North Pekin Water System

MyTapWater.org's tap water quality report is the compilation of data collected from federal, state, and local government agencies, most prominently the EPA. We strive to populate the report with the latest data concerning water contaminants, lead and copper levels, and water quality violations. We only collect drinking water data from public water systems.

PWS Service Information
PWS ID: IL1790550
Type: Community water system
EPA Region: 05
Primary Service Area: Municipality
Primary Source: Ground water
Population Served: 1,573
Contact Information
LANDRITH, DEBORAH
LANDRITH, DEBORAH
318 N MAIN STREET
NORTH PEKIN, IL 61554
[email protected]

This public water system services 1 municipality in 1 county.

Summary Results


A summary view of tests in which a water contaminant found to exceed the Maximum Contaminant Level (MCL) set by the EPA.

Maximum Contaminant Levels Exceeded (by year):

2013   (0) 2014   (0) 2015   (1) 2016   (0) 2017   (0) 2018   (0)
chlorate

Contaminant Detailed Results


This a view of violations of maximum contaminant levels. Use the expanded view see result data for a drinking water contaminant, the minimum level that can be recognized in a test (MRL), and upper limit that is considered healthy (HRL).

chlorate

Year Test Date MRLMinimum Reporting Level HRLHealth Risk Limit Test Result
2015 2015-12-10 20 210 < 20
2015 2015-12-10 20 210 409
2015 2015-12-10 20 210 99.4
2015 2015-06-10 20 210 < 20
2015 2015-06-10 20 210 23.478
2015 2015-06-10 20 210 23.638

Other Water Contaminants Tested


The following contaminants were tested and found to be within national EPA guidelines.

Contaminant MRLMinimum Reporting Level HRLHealth Risk Limit Avg Result
1,1-dichloroethane 0.03 6.14 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.03 6.14 < 0.03
2015 2015-12-10 0.03 6.14 < 0.03
2015 2015-06-10 0.03 6.14 < 0.03
2015 2015-06-10 0.03 6.14 < 0.03
1,2,3-trichloropropane 0.03 0.0004 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.03 0.0004 < 0.03
2015 2015-12-10 0.03 0.0004 < 0.03
2015 2015-06-10 0.03 0.0004 < 0.03
2015 2015-06-10 0.03 0.0004 < 0.03
1,3-butadiene 0.1 0.0103 < 0.1 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.1 0.0103 < 0.1
2015 2015-12-10 0.1 0.0103 < 0.1
2015 2015-06-10 0.1 0.0103 < 0.1
2015 2015-06-10 0.1 0.0103 < 0.1
1,4-dioxane 0.07 0.35 < 0.07 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.07 0.35 < 0.07
2015 2015-12-10 0.07 0.35 < 0.07
2015 2015-06-10 0.07 0.35 < 0.07
2015 2015-06-10 0.07 0.35 < 0.07
bromomethane 0.2 140 < 0.2 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.2 140 < 0.2
2015 2015-12-10 0.2 140 < 0.2
2015 2015-06-10 0.2 140 < 0.2
2015 2015-06-10 0.2 140 < 0.2
chloromethane 0.2 2.69 < 0.2 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.2 2.69 < 0.2
2015 2015-12-10 0.2 2.69 < 0.2
2015 2015-06-10 0.2 2.69 < 0.2
2015 2015-06-10 0.2 2.69 < 0.2
chromium 0.2 100 0.642 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.2 100 0.935
2015 2015-12-10 0.2 100 < 0.2
2015 2015-12-10 0.2 100 0.835
2015 2015-06-10 0.2 100 1.08
2015 2015-06-10 0.2 100 < 0.2
2015 2015-06-10 0.2 100 1.002
cobalt 1 70 0.615 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 1 70 < 1
2015 2015-12-10 1 70 1.8
2015 2015-12-10 1 70 < 1
2015 2015-06-10 1 70 < 1
2015 2015-06-10 1 70 1.89
2015 2015-06-10 1 70 < 1
Halon 1011 0.06 90 < 0.06 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.06 90 < 0.06
2015 2015-12-10 0.06 90 < 0.06
2015 2015-06-10 0.06 90 < 0.06
2015 2015-06-10 0.06 90 < 0.06
HCFC-22 0.08 0 < 0.08 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.08 0 < 0.08
2015 2015-12-10 0.08 0 < 0.08
2015 2015-06-10 0.08 0 < 0.08
2015 2015-06-10 0.08 0 < 0.08
manganese 1 0 108.0452 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 1 0 < 1
2015 2015-12-10 1 0 300
2015 2015-12-10 1 0 2.72
2015 2015-06-10 1 0 < 1
2015 2015-06-10 1 0 342.284
2015 2015-06-10 1 0 3.267
molybdenum 1 40 3.0912 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 1 40 < 1
2015 2015-12-10 1 40 7.82
2015 2015-12-10 1 40 1.56
2015 2015-06-10 1 40 < 1
2015 2015-06-10 1 40 7.717
2015 2015-06-10 1 40 1.45
PFBS 0.09 0 < 0.09 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.09 0 < 0.09
2015 2015-12-10 0.09 0 < 0.09
2015 2015-06-10 0.09 0 < 0.09
2015 2015-06-10 0.09 0 < 0.09
PFHpA 0.01 0 < 0.01 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.01 0 < 0.01
2015 2015-12-10 0.01 0 < 0.01
2015 2015-06-10 0.01 0 < 0.01
2015 2015-06-10 0.01 0 < 0.01
PFHxS 0.03 0 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.03 0 < 0.03
2015 2015-12-10 0.03 0 < 0.03
2015 2015-06-10 0.03 0 < 0.03
2015 2015-06-10 0.03 0 < 0.03
PFNA 0.02 0 < 0.02 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.02 0 < 0.02
2015 2015-12-10 0.02 0 < 0.02
2015 2015-06-10 0.02 0 < 0.02
2015 2015-06-10 0.02 0 < 0.02
PFOA 0.02 0.07 < 0.02 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.02 0.07 < 0.02
2015 2015-12-10 0.02 0.07 < 0.02
2015 2015-06-10 0.02 0.07 < 0.02
2015 2015-06-10 0.02 0.07 < 0.02
PFOS 0.04 0.07 < 0.04 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.04 0.07 < 0.04
2015 2015-12-10 0.04 0.07 < 0.04
2015 2015-06-10 0.04 0.07 < 0.04
2015 2015-06-10 0.04 0.07 < 0.04
sec-butylbenzene 0.04 0 < 0.04 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.04 0 < 0.04
2015 2015-12-10 0.04 0 < 0.04
2015 2015-06-10 0.04 0 < 0.04
2015 2015-06-10 0.04 0 < 0.04
strontium 0.3 1500 154.4128 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.3 1500 146
2015 2015-12-10 0.3 1500 188
2015 2015-12-10 0.3 1500 151
2015 2015-06-10 0.3 1500 137.117
2015 2015-06-10 0.3 1500 167.058
2015 2015-06-10 0.3 1500 137.302
vanadium 0.2 21 0.4678 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.2 21 0.747
2015 2015-12-10 0.2 21 < 0.2
2015 2015-12-10 0.2 21 0.507
2015 2015-06-10 0.2 21 0.816
2015 2015-06-10 0.2 21 < 0.2
2015 2015-06-10 0.2 21 0.737
chromium-6 0.03 0 0.706 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-12-10 0.03 0 1.11
2015 2015-12-10 0.03 0 < 0.03
2015 2015-12-10 0.03 0 0.987
2015 2015-08-10 0.03 0 1.1
2015 2015-07-13 0.03 0 < 0.03
2015 2015-06-10 0.03 0 1.039

Lead and Copper Data


Lead and copper are recorded separately from other contaminants because of the Lead and Copper Rule. As with all other results, these are the findings at the water supply level. Lead and copper can be — and often are — deposited in drinking water in between the water facility and your tap.

Sample ID Contaminant Sampling Start Date Sampling End Date Result
IL45156 lead 2014-01-01 2016-12-31 0.0026mg/L
IL41053 lead 2011-01-01 2013-12-31 0.0024mg/L
IL36461 lead 2008-01-01 2010-12-31 0.002mg/L

Violations


Known violations of the Safe Drinking Water Act as recorded by the EPA.

Compliance Dates Rule Violation Type Contaminant Name Status
- N/A Nitrates Maximum Contaminant Level Violation, Average Nitrate Returned to Compliance
- N/A Radionuclides Monitoring, Regular Gross Alpha, Excl. Radon and U Known

Local Water Testing


Find a lab in your area so you can get your tap or well water tested. This list contains both governmental and private labs, all of which are EPA-certified for drinking water testing.

Unable to identify any nearby water testing labs near 61554.

Water Bill Information


Convenient information about your water service.

Unable to identify any billing information about North Pekin (IL1790550).

What My Water Data Means


Water data isn't always easy to interpret, but by following the links on this page you should be able to have most of your questions answered. By clicking the name of a water contaminant or secondary substance you can learn about that specific substance. Ultimately this page should give you some insight towards learning if your water is safe, what water filter you should buy (if any), and how well your local water compares against other sources.

Sources


The origin of MyTapWater.org's water data is explained on our Data Sources page.

Why Is My Water Data Not More Recent?


The recency of the data for your ZIP code depends on the last your water source was tested, by a federal, state, or local agency. More information about the timing can be determined by learning about the dataset in question and seeing how often the EPA (other another governing body) mandated testing.