Public Water System: Ormond Beach

MyTapWater.org's tap water quality report is the compilation of data collected from federal, state, and local government agencies, most prominently the EPA. We strive to populate the report with the latest data concerning water contaminants, lead and copper levels, and water quality violations. We only collect drinking water data from public water systems.

PWS Service Information
PWS ID: FL3640963
Type: Community water system
EPA Region: 04
Primary Service Area: Municipality
Primary Source: Ground water
Population Served: 50,632
Contact Information
CITY OF ORMOND BEACH
DAVID PONITZ, P.E.
ORMOND BEACH PUBLIC WORKS DEPARTMENT
POST OFFICE BOX 277
ORMOND BEACH, FL 32175-0277

This public water system services 3 zip codes in 1 municipality in 1 county.

Summary Results


A summary view of the the times a water contaminant was tested and found to exceed the level set by the EPA (the MCL).

Maximum Contaminant Levels Exceeded (by year):

2013   (0) 2014   (1) 2015   (1)
chlorate chlorate

Contaminant Detailed Results


This a view of violations of maximum contaminant levels. In the expanded view you can see each know test date for a given contaminant, the result of the test, the minimum level that can be recognized in a test (MRL), and upper limit that is considered healthy (HRL).

chlorate
Is this in your home's pipes?

Year Test Date MRL HRL Test Result
2015 2015-05-13 20 210 323
2015 2015-05-13 20 210 350
2014 2014-11-18 20 210 346
2014 2014-11-18 20 210 321

Other Water Contaminants Tested


The following contaminants were tested and within national EPA guidelines.

The last mile of pipe makes a big difference, learn more about testing your water.

Contaminant MRL HRL Avg Result
cobalt 1 70 < 1 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 1 70 < 1
2015 2015-05-13 1 70 < 1
2014 2014-11-18 1 70 < 1
2014 2014-11-18 1 70 < 1
1,3-butadiene 0.1 0.0103 < 0.1 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.1 0.0103 < 0.1
2014 2014-11-18 0.1 0.0103 < 0.1
strontium 0.3 1500 123.5 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.3 1500 141
2015 2015-05-13 0.3 1500 123
2014 2014-11-18 0.3 1500 125
2014 2014-11-18 0.3 1500 105
Halon 1011 0.06 90 < 0.06 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.06 90 < 0.06
2014 2014-11-18 0.06 90 < 0.06
1,2,3-trichloropropane 0.03 0.0004 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.03 0.0004 < 0.03
2014 2014-11-18 0.03 0.0004 < 0.03
bromomethane 0.2 140 < 0.2 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.2 140 < 0.2
2014 2014-11-18 0.2 140 < 0.2
1,4-dioxane 0.07 0.35 < 0.07 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.07 0.35 < 0.07
2014 2014-11-18 0.07 0.35 < 0.07
vanadium 0.2 21 0.425 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.2 21 0.44
2015 2015-05-13 0.2 21 0.44
2014 2014-11-18 0.2 21 0.34
2014 2014-11-18 0.2 21 0.48
chromium 0.2 100 0.8675 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.2 100 0.38
2015 2015-05-13 0.2 100 0.36
2014 2014-11-18 0.2 100 2.3
2014 2014-11-18 0.2 100 0.43
chromium-6 0.03 0 0.135 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.03 0 0.11
2015 2015-05-13 0.03 0 0.11
2014 2014-11-18 0.03 0 0.16
2014 2014-11-18 0.03 0 0.16
molybdenum 1 40 < 1 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 1 40 < 1
2015 2015-05-13 1 40 < 1
2014 2014-11-18 1 40 < 1
2014 2014-11-18 1 40 < 1
HCFC-22 0.08 0 < 0.08 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.08 0 < 0.08
2014 2014-11-18 0.08 0 < 0.08
17-alpha-ethynylestradiol 0.0009 0.035 < 0.0009 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.0009 0.035 < 0.0009
chloromethane 0.2 2.69 < 0.2 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.2 2.69 < 0.2
2014 2014-11-18 0.2 2.69 < 0.2
PFOS 0.04 0.07 < 0.04 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.04 0.07 < 0.04
2014 2014-11-18 0.04 0.07 < 0.04
17-beta-estradiol 0.0004 0.0009 < 0.0004 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.0004 0.0009 < 0.0004
1,1-dichloroethane 0.03 6.14 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.03 6.14 < 0.03
2014 2014-11-18 0.03 6.14 < 0.03
PFOA 0.02 0.07 < 0.02 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.02 0.07 < 0.02
2014 2014-11-18 0.02 0.07 < 0.02
PFHxS 0.03 0 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.03 0 < 0.03
2014 2014-11-18 0.03 0 < 0.03
equilin 0.004 0.35 < 0.004 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.004 0.35 < 0.004
PFHpA 0.01 0 < 0.01 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.01 0 < 0.01
2014 2014-11-18 0.01 0 < 0.01
estriol 0.0008 0.35 < 0.0008 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.0008 0.35 < 0.0008
PFBS 0.09 0 < 0.09 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.09 0 < 0.09
2014 2014-11-18 0.09 0 < 0.09
PFNA 0.02 0 < 0.02 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.02 0 < 0.02
2014 2014-11-18 0.02 0 < 0.02
estrone 0.002 0.35 < 0.002 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.002 0.35 < 0.002
testosterone 0.0001 0 < 0.0001 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.0001 0 < 0.0001
4-androstene-3,17-dione 0.0003 0 < 0.0003 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-05-13 0.0003 0 < 0.0003

Lead and Copper Data


Lead and copper are recorded separately from other contaminants because of the Lead and Copper Rule. As with all other results, these are the findings at the water supply. Lead and copper can be — and often are — added to drinking water in between the water facility and a tap.

Sample ID Contaminant Sampling Start Date Sampling End Date Result
FL137262 lead 2014-01-01 2014-12-01 0.0052mg/L
FL122317 lead 2012-01-01 2012-12-01 0.0042mg/L
FL114236 lead 2011-01-01 2011-12-01 0.0062mg/L
FL109102 lead 2010-01-01 2010-12-01 0.012mg/L
FL93942 lead 2009-01-01 2009-06-01 0.0051mg/L
FL91539 lead 2008-07-01 2008-12-01 0.0082mg/L

Violations


Known violations of the Safe Drinking Water Act as recorded by the EPA.

Compliance Dates Rule Violation Type Contaminant Name Status
2008-11-01 - 2008-11-30 Total Coliform Rule Monitoring, Repeat Minor (TCR) Coliform (TCR) Known
2003-06-01 - 2003-06-30 Total Coliform Rule Maximum Contaminant Level Violation, Monthly (TCR) Coliform (TCR) Known
2002-01-01 - 2002-12-31 Nitrates Monitoring, Regular Nitrate Known
2002-09-01 - 2002-09-30 Total Coliform Rule Monitoring, Repeat Major (TCR) Coliform (TCR) Known
2004-07-01 - N/A Consumer Confidence Rule Consumer Confidence Report Complete Failure to Report Consumer Confidence Rule Open
2004-08-10 - N/A Consumer Confidence Rule Consumer Confidence Report Inadequate Reporting Consumer Confidence Rule Open

What My Water Data Means


Water data isn't always easy to interpret, but by following the links on this page you should be able to have most of your questions answered. By clicking the name of a water contaminant or secondary substance you can learn about that specific substance. Ultimately this page should give you some insight towards learning if your water is safe, what water filter you should buy (if any), and how well your local water compares against other sources.

Sources


The origin of MyTapWater.org's water data is explained on our Data Sources page.

Why Is My Water Data Not More Recent?


The recency of the data for your ZIP code depends on the last your water source was tested, by a federal, state, or local agency. More information about the timing can be determined by learning about the dataset in question and seeing how often the EPA (other another governing body) mandated testing.