Public Water System: Nas Pensacola / Corry Station

MyTapWater.org's tap water quality report is the compilation of data collected from federal, state, and local government agencies, most prominently the EPA. We strive to populate the report with the latest data concerning water contaminants, lead and copper levels, and water quality violations. We only collect drinking water data from public water systems.

PWS Service Information
PWS ID: FL1170814
Type: Community water system
EPA Region: 04
Primary Service Area: Institution
Primary Source: Ground water
Population Served: 22,600
Contact Information
COMMANDER BRENT PAUL
COMMANDER BRENT PAUL
190 RADFORD BOULEVARD (CODE 00600)
NAS PENSACOLA, FL 32508-5303

This public water system services 1 zip code in 1 municipality in 1 county.

Summary Results


A summary view of the the times a water contaminant was tested and found to exceed the level set by the EPA (the MCL).

Maximum Contaminant Levels Exceeded (by year):

2013   (0) 2014   (0) 2015   (1)
chlorate

Contaminant Detailed Results


This a view of violations of maximum contaminant levels. In the expanded view you can see each know test date for a given contaminant, the result of the test, the minimum level that can be recognized in a test (MRL), and upper limit that is considered healthy (HRL).

chlorate
Is this in your home's pipes?

Year Test Date MRL HRL Test Result
2015 2015-08-06 20 210 736
2015 2015-08-06 20 210 729
2015 2015-02-18 20 210 279
2015 2015-02-18 20 210 180

Other Water Contaminants Tested


The following contaminants were tested and within national EPA guidelines.

The last mile of pipe makes a big difference, learn more about testing your water.

Contaminant MRL HRL Avg Result
molybdenum 1 40 < 1 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 1 40 < 1
2015 2015-08-06 1 40 < 1
2015 2015-02-18 1 40 < 1
2015 2015-02-18 1 40 < 1
chromium 0.2 100 < 0.2 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.2 100 < 0.2
2015 2015-08-06 0.2 100 < 0.2
2015 2015-02-18 0.2 100 < 0.2
2015 2015-02-18 0.2 100 < 0.2
strontium 0.3 1500 20.275 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.3 1500 16.5
2015 2015-08-06 0.3 1500 18
2015 2015-02-18 0.3 1500 27.1
2015 2015-02-18 0.3 1500 19.5
chromium-6 0.03 0 0.1285 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.03 0 0.22
2015 2015-08-06 0.03 0 0.2
2015 2015-02-18 0.03 0 < 0.03
2015 2015-02-18 0.03 0 0.094
cobalt 1 70 < 1 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 1 70 < 1
2015 2015-08-06 1 70 < 1
2015 2015-02-18 1 70 < 1
2015 2015-02-18 1 70 < 1
chloromethane 0.2 2.69 < 0.2 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.2 2.69 < 0.2
2015 2015-02-18 0.2 2.69 < 0.2
1,4-dioxane 0.07 0.35 0.115 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.07 0.35 0.13
2015 2015-02-18 0.07 0.35 0.1
PFOA 0.02 0.07 < 0.02 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.02 0.07 < 0.02
2015 2015-02-18 0.02 0.07 < 0.02
vanadium 0.2 21 < 0.2 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.2 21 < 0.2
2015 2015-08-06 0.2 21 < 0.2
2015 2015-02-18 0.2 21 < 0.2
2015 2015-02-18 0.2 21 < 0.2
bromomethane 0.2 140 < 0.2 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.2 140 < 0.2
2015 2015-02-18 0.2 140 < 0.2
1,1-dichloroethane 0.03 6.14 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.03 6.14 < 0.03
2015 2015-02-18 0.03 6.14 < 0.03
PFHxS 0.03 0 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.03 0 < 0.03
2015 2015-02-18 0.03 0 < 0.03
PFNA 0.02 0 < 0.02 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.02 0 < 0.02
2015 2015-02-18 0.02 0 < 0.02
1,3-butadiene 0.1 0.0103 < 0.1 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.1 0.0103 < 0.1
2015 2015-02-18 0.1 0.0103 < 0.1
PFOS 0.04 0.07 < 0.04 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.04 0.07 < 0.04
2015 2015-02-18 0.04 0.07 < 0.04
HCFC-22 0.08 0 < 0.08 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.08 0 < 0.08
2015 2015-02-18 0.08 0 < 0.08
Halon 1011 0.06 90 < 0.06 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.06 90 < 0.06
2015 2015-02-18 0.06 90 < 0.06
1,2,3-trichloropropane 0.03 0.0004 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.03 0.0004 < 0.03
2015 2015-02-18 0.03 0.0004 < 0.03
PFHpA 0.01 0 < 0.01 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.01 0 < 0.01
2015 2015-02-18 0.01 0 < 0.01
PFBS 0.09 0 < 0.09 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-08-06 0.09 0 < 0.09
2015 2015-02-18 0.09 0 < 0.09

Lead and Copper Data


Lead and copper are recorded separately from other contaminants because of the Lead and Copper Rule. As with all other results, these are the findings at the water supply. Lead and copper can be — and often are — added to drinking water in between the water facility and a tap.

Sample ID Contaminant Sampling Start Date Sampling End Date Result
FL136242 lead 2014-01-01 2014-12-01 0.0009mg/L
FL114374 lead 2011-01-01 2011-12-01 0.0029mg/L
FL95522 lead 2009-01-01 2009-12-01 0.0011mg/L

Violations


Known violations of the Safe Drinking Water Act as recorded by the EPA.

Compliance Dates Rule Violation Type Contaminant Name Status
2017-04-01 - 2017-06-30 Radionuclides Maximum Contaminant Level Violation, Average Combined Radium (-226 and -228) Known
2014-05-01 - 2014-05-31 Ground Water Rule Failure to Conduct Assessment Monitoring E. COLI Returned to Compliance
2008-06-01 - 2008-06-30 Total Coliform Rule Maximum Contaminant Level Violation, Monthly (TCR) Coliform (TCR) Known
2004-06-01 - 2004-06-30 Total Coliform Rule Monitoring, Repeat Major (TCR) Coliform (TCR) Known
2000-06-01 - 2000-06-30 Total Coliform Rule Maximum Contaminant Level Violation, Monthly (TCR) Coliform (TCR) Known
1999-07-01 - 1999-07-31 Total Coliform Rule Monitoring, Repeat Minor (TCR) Coliform (TCR) Known
1994-08-01 - 1994-08-31 Total Coliform Rule Monitoring, Repeat Minor (TCR) Coliform (TCR) Known
1993-10-01 - 1993-10-31 Total Coliform Rule Monitoring, Routine Major (TCR) Coliform (TCR) Known
1992-04-01 - 1992-04-30 Total Coliform Rule Monitoring, Routine Minor (TCR) Coliform (TCR) Known

What My Water Data Means


Water data isn't always easy to interpret, but by following the links on this page you should be able to have most of your questions answered. By clicking the name of a water contaminant or secondary substance you can learn about that specific substance. Ultimately this page should give you some insight towards learning if your water is safe, what water filter you should buy (if any), and how well your local water compares against other sources.

Sources


The origin of MyTapWater.org's water data is explained on our Data Sources page.

Why Is My Water Data Not More Recent?


The recency of the data for your ZIP code depends on the last your water source was tested, by a federal, state, or local agency. More information about the timing can be determined by learning about the dataset in question and seeing how often the EPA (other another governing body) mandated testing.