Cullman Water Works, City Of Water System

MyTapWater.org's tap water quality report is the compilation of data collected from federal, state, and local government agencies, most prominently the EPA. We strive to populate the report with the latest data concerning water contaminants, lead and copper levels, and water quality violations. We only collect drinking water data from public water systems.

PWS Service Information
PWS ID: AL0001786
Type: Community water system
EPA Region: 04
Primary Service Area: Residential Area
Primary Source: Surface water purchased
Population Served: 35,922
Contact Information
JACOBS, WOODY
JACOBS, WOODY
P O Box 278
CULLMAN, AL 35056

This public water system services 1 municipality in 1 county.

Summary Results


A summary view of tests in which a water contaminant found to exceed the Maximum Contaminant Level (MCL) set by the EPA.

Maximum Contaminant Levels Exceeded (by year):

2013   (0) 2014   (0) 2015   (1) 2016   (0) 2017   (0) 2018   (0)
chlorate

Contaminant Detailed Results


This a view of violations of maximum contaminant levels. Use the expanded view see result data for a drinking water contaminant, the minimum level that can be recognized in a test (MRL), and upper limit that is considered healthy (HRL).

chlorate

Year Test Date MRLMinimum Reporting Level HRLHealth Risk Limit Test Result
2015 2015-11-05 20 210 300
2015 2015-11-05 20 210 450
2015 2015-08-06 20 210 330
2015 2015-08-06 20 210 460
2015 2015-05-22 20 210 280
2015 2015-05-22 20 210 320
2015 2015-02-24 20 210 160
2015 2015-02-24 20 210 220

Other Water Contaminants Tested


The following contaminants were tested and found to be within national EPA guidelines.

Contaminant MRLMinimum Reporting Level HRLHealth Risk Limit Avg Result
1,1-dichloroethane 0.03 6.14 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.03 6.14 < 0.03
2015 2015-08-06 0.03 6.14 < 0.03
2015 2015-05-22 0.03 6.14 < 0.03
2015 2015-02-24 0.03 6.14 < 0.03
1,2,3-trichloropropane 0.03 0.0004 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.03 0.0004 < 0.03
2015 2015-08-06 0.03 0.0004 < 0.03
2015 2015-05-22 0.03 0.0004 < 0.03
2015 2015-02-24 0.03 0.0004 < 0.03
1,3-butadiene 0.1 0.0103 < 0.1 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.1 0.0103 < 0.1
2015 2015-08-06 0.1 0.0103 < 0.1
2015 2015-05-22 0.1 0.0103 < 0.1
2015 2015-02-24 0.1 0.0103 < 0.1
1,4-dioxane 0.07 0.35 < 0.07 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.07 0.35 < 0.07
2015 2015-08-06 0.07 0.35 < 0.07
2015 2015-05-22 0.07 0.35 < 0.07
2015 2015-02-24 0.07 0.35 < 0.07
bromomethane 0.2 140 < 0.2 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.2 140 < 0.2
2015 2015-08-06 0.2 140 < 0.2
2015 2015-05-22 0.2 140 < 0.2
2015 2015-02-24 0.2 140 < 0.2
chloromethane 0.2 2.69 < 0.2 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.2 2.69 < 0.2
2015 2015-08-06 0.2 2.69 < 0.2
2015 2015-05-22 0.2 2.69 < 0.2
2015 2015-02-24 0.2 2.69 < 0.2
chromium 0.2 100 0.1125 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.2 100 0.2
2015 2015-11-05 0.2 100 0.3
2015 2015-08-06 0.2 100 0.2
2015 2015-08-06 0.2 100 0.2
2015 2015-05-22 0.2 100 < 0.2
2015 2015-05-22 0.2 100 < 0.2
2015 2015-02-24 0.2 100 < 0.2
2015 2015-02-24 0.2 100 < 0.2
chromium-6 0.03 0 0.14 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.03 0 0.18
2015 2015-11-05 0.03 0 0.26
2015 2015-08-06 0.03 0 0.23
2015 2015-08-06 0.03 0 0.22
2015 2015-05-22 0.03 0 0.07
2015 2015-05-22 0.03 0 0.11
2015 2015-02-24 0.03 0 < 0.03
2015 2015-02-24 0.03 0 0.05
cobalt 1 70 < 1 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 1 70 < 1
2015 2015-11-05 1 70 < 1
2015 2015-08-06 1 70 < 1
2015 2015-08-06 1 70 < 1
2015 2015-05-22 1 70 < 1
2015 2015-05-22 1 70 < 1
2015 2015-02-24 1 70 < 1
2015 2015-02-24 1 70 < 1
Halon 1011 0.06 90 < 0.06 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.06 90 < 0.06
2015 2015-08-06 0.06 90 < 0.06
2015 2015-05-22 0.06 90 < 0.06
2015 2015-02-24 0.06 90 < 0.06
HCFC-22 0.08 0 < 0.08 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.08 0 < 0.08
2015 2015-08-06 0.08 0 < 0.08
2015 2015-05-22 0.08 0 < 0.08
2015 2015-02-24 0.08 0 < 0.08
molybdenum 1 40 < 1 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 1 40 < 1
2015 2015-11-05 1 40 < 1
2015 2015-08-06 1 40 < 1
2015 2015-08-06 1 40 < 1
2015 2015-05-22 1 40 < 1
2015 2015-05-22 1 40 < 1
2015 2015-02-24 1 40 < 1
2015 2015-02-24 1 40 < 1
PFBS 0.09 0 < 0.09 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.09 0 < 0.09
2015 2015-08-06 0.09 0 < 0.09
2015 2015-05-22 0.09 0 < 0.09
2015 2015-02-24 0.09 0 < 0.09
PFHpA 0.01 0 < 0.01 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.01 0 < 0.01
2015 2015-08-06 0.01 0 < 0.01
2015 2015-05-22 0.01 0 < 0.01
2015 2015-02-24 0.01 0 < 0.01
PFHxS 0.03 0 < 0.03 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.03 0 < 0.03
2015 2015-08-06 0.03 0 < 0.03
2015 2015-05-22 0.03 0 < 0.03
2015 2015-02-24 0.03 0 < 0.03
PFNA 0.02 0 < 0.02 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.02 0 < 0.02
2015 2015-08-06 0.02 0 < 0.02
2015 2015-05-22 0.02 0 < 0.02
2015 2015-02-24 0.02 0 < 0.02
PFOA 0.02 0.07 < 0.02 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.02 0.07 < 0.02
2015 2015-08-06 0.02 0.07 < 0.02
2015 2015-05-22 0.02 0.07 < 0.02
2015 2015-02-24 0.02 0.07 < 0.02
PFOS 0.04 0.07 < 0.04 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.04 0.07 < 0.04
2015 2015-08-06 0.04 0.07 < 0.04
2015 2015-05-22 0.04 0.07 < 0.04
2015 2015-02-24 0.04 0.07 < 0.04
strontium 0.3 1500 29.625 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.3 1500 32
2015 2015-11-05 0.3 1500 36
2015 2015-08-06 0.3 1500 29
2015 2015-08-06 0.3 1500 31
2015 2015-05-22 0.3 1500 27
2015 2015-05-22 0.3 1500 30
2015 2015-02-24 0.3 1500 25
2015 2015-02-24 0.3 1500 27
vanadium 0.2 21 0.1625 [+] Expand Test Data
Year Test Date MRL HRL Test Result
2015 2015-11-05 0.2 21 0.2
2015 2015-11-05 0.2 21 0.3
2015 2015-08-06 0.2 21 < 0.2
2015 2015-08-06 0.2 21 < 0.2
2015 2015-05-22 0.2 21 0.3
2015 2015-05-22 0.2 21 0.3
2015 2015-02-24 0.2 21 < 0.2
2015 2015-02-24 0.2 21 0.2

Lead and Copper Data


Lead and copper are recorded separately from other contaminants because of the Lead and Copper Rule. As with all other results, these are the findings at the water supply level. Lead and copper can be — and often are — deposited in drinking water in between the water facility and your tap.

Sample ID Contaminant Sampling Start Date Sampling End Date Result
AL102113 lead 2014-01-01 2016-12-31 0.0024mg/L
AL80167 lead 2011-01-01 2013-12-31 0.00462mg/L
AL57561 lead 2008-01-01 2010-12-31 0.00242mg/L

Violations


Known violations of the Safe Drinking Water Act as recorded by the EPA.

Compliance Dates Rule Violation Type Contaminant Name Status
2002-12-01 - 2002-12-31 Total Coliform Rule Maximum Contaminant Level Violation, Monthly (TCR) Coliform (TCR) Known

Local Water Testing


Find a lab in your area so you can get your tap or well water tested. This list contains both governmental and private labs, all of which are EPA-certified for drinking water testing.

Lab Location Zip Code
Alabama Power Company General Testing Laboratory Calera, AL 35040
Martin County Environmental Services – North Water Treatment Plant Laboratory Jensen Beach, FL 34957
City of Port St. Lucie Utility Systems Department Port St. Lucie, FL 34986

Water Bill Information


Convenient information about your water service.

Unable to identify any billing information about Cullman Water Works, City Of (AL0001786).

What My Water Data Means


Water data isn't always easy to interpret, but by following the links on this page you should be able to have most of your questions answered. By clicking the name of a water contaminant or secondary substance you can learn about that specific substance. Ultimately this page should give you some insight towards learning if your water is safe, what water filter you should buy (if any), and how well your local water compares against other sources.

Sources


The origin of MyTapWater.org's water data is explained on our Data Sources page.

Why Is My Water Data Not More Recent?


The recency of the data for your ZIP code depends on the last your water source was tested, by a federal, state, or local agency. More information about the timing can be determined by learning about the dataset in question and seeing how often the EPA (other another governing body) mandated testing.